  • B) Duct Sensor - For single point monitoring. It is available with various probe lengths and enclosures to fit any application.


    D) Duct Average Sensor - Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors.


    F) OSA Sensor - Comes in a weatherproof enclosure. It incorporates a sun/wind shield to protect the sensor and provide accurate readings.
     




    The TE Series Temperature sensors offer a choice of precision platinum RTD's, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system.

    The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications.

    The single point sensors are encapsulated in a 6.35 mm (0.25") OD 304 stainless steel probe.  All probes are constructed to provide good heat transfer and fast response.  The averaging sensors are available in both plenum rated cable or with a copper probe.




    C) Immersion Sensor - Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a 1/2" NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles.

    E) Strap-on Sensor - Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed.


    FD) Flex-Duct Sensor -Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors.





    The TE500 transmitter option is standard with the 1000 ohm platinum sensor and provides either 4-20mA, 0-5 VDC or 0-10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100 ohm platinum sensor transmitter is optional.


    Transmitter General Specifications:
    Supply Voltage:
    Output:
    Accuracy:
    Operating Temp.:
    OSA Operating Temp.:

    24 VDC/VAC
    4-20mA, 0-5 VDC or 0-10 VDC
    0.1% of span
    0C-70C (32F-158F)
    -40C-85C (-40F-185F)